What each zone is for, the two structural bands, and how Linked zones works.
The five zones
Zone
Holds
Notes
Zone D — Condensation-Risk Ducts
Standard HVAC ducts
A standard duct is flagged if it sits over Zone A's width
Zone E — Low-Condensation-Risk Ducts
Ducts flagged Low Condensation Risk Duct
May pass over Zone A
Zone A — Electrical Services
Cable trays
Zone B — Access & Maintenance
Kept clear — this is the access corridor a technician stands in to reach the services around it
Zone C — Piped Services
Pipes
Two further bands appear in the section but aren't zones you place services in directly:
the Structural Beam Band at the top of the void, and the Ceiling Device Drops Band
at the bottom, reserved for vertical drops to fittings below the ceiling.
Turning a zone off
Each zone has an Enabled checkbox in its properties. Turning a zone off drops it from
the drawing and from the coordination checks — but a zone that still holds services can't be
disabled until you remove or move them out first.
Linked zones
Linked zones (on by default for a new document) keeps the zones attached edge to edge
and filling the void: resizing one zone moves its neighbours so there's never a gap or an
overlap. Turn it off in Project Settings to position each zone independently.
The access corridor (Zone B)
Zone B has to stay wide enough to work in, and it has to sit next to Zone A so the trays in
it are reachable:
Below the Zone B minimum width threshold (Tool Default: 600 mm), the corridor is
flagged as too narrow to work in. At exactly the minimum it's flagged as a warning instead
— there's no margin left for a later change to narrow it further.
If Zone B doesn't share an edge with Zone A, every tray in Zone A is flagged as
unreachable.
A cable tray whose centreline sits further than the Arm's reach limit (Tool Default:
900 mm) from the nearest Zone B edge is flagged — it can only be reached by leaning into
the void.
These thresholds are project-editable — see Rule set.
The checks themselves are covered in full on
Compliance checks.
Low Condensation Risk ducts
A duct flagged Low Condensation Risk Duct goes into Zone E instead of Zone D and is
allowed to pass over Zone A's width — a standard duct is not, because it can shed
condensate onto whatever sits below it. See
Ducts, trays & pipes.