Fittings and Σ K — MEP Tools

The two Σ K modes, the full default K library, and how to override a K value per row.

Fitting losses are calculated as Δp = Σ K · ½ρv², where v is the actual duct velocity. Card 04 — Fittings offers two mutually exclusive ways to arrive at Σ K.

Manual Sigma K

Enter one combined coefficient in Total fitting coefficient (Σ K). Use this when you already have a Σ K from another source, or when you only want the straight-run friction (leave it at the default 0).

Manual mode also hosts the Duct role (advisory) selector:

RoleAdvisory band
Main duct5–8 m/s
Branch / near terminal3–6 m/s
Not selectedno band, no verdict

The band drives the velocity gauge and the band warnings only — it never changes the calculated pressure drop.

As-built quirk: the role selector is rendered only in Manual Σ K mode. Switching to Schedule hides it, and the role you last chose stays active in the gauge. To clear or change a role while working in Schedule mode, switch back to Manual, set the role, then switch across again.

Schedule

Pick a fitting from the dropdown and select + Add row. Each row carries a quantity, the library default K, an optional override, and its Σ contribution (K × quantity). The table foot totals Computed Σ K (schedule) live, and the delete button removes a row.

Switching modes does not delete anything: your schedule rows survive a trip through Manual mode, and vice versa. Only the active mode's Σ K is applied.

As-built quirk: a PDF report prints the fitting schedule table whenever any rows exist — including while Manual Σ K is the active mode, where those rows contribute nothing. Check the report's Σ K mode row to see which figure was actually applied.

The default K library

Version mvp_default_v1. These are simplified typical figures for preliminary checking. They are not reproduced from a named standard, are not specific to any manufacturer, and are not adjusted for the geometry of your particular fitting. Override them per row for manufacturer or project-specific data.

CategoryFittingDefault K
Bends / elbows90 deg bend — long radius0.2
Bends / elbows90 deg bend — short radius0.5
Bends / elbows45 deg bend0.15
Bends / elbows90 deg elbow — mitred1.3
Tees / branchesTee — straight through0.2
Tees / branchesTee — branch take-off1.0
Tees / branchesWye / lateral 45 deg0.3
TransitionsTransition — gradual0.2
TransitionsTransition — abrupt0.6
Entry / exitEntry — sharp-edged0.5
Entry / exitEntry — bellmouth0.05
Entry / exitExit — to plenum/space1.0
DampersBalancing damper (open)0.3
DampersFire damper1.5
DampersVolume control damper0.6
Silencers / attenuatorsSilencer / attenuator1.0
Flexible connectionsFlexible connection (short)0.5
TerminalsGrille / diffuser (typical)2.0
FiltersFilter (clean, typical)2.0
CustomCustom fitting— (override required)

The library version is stamped into the PDF report and into every share link, so a saved calculation records which K set produced it.

Choosing between the modes

Manual Σ K is faster and is the right choice when a figure is handed to you. The schedule is worth the extra typing when you need the audit trail: the PDF report lists every row with its quantity, effective K, contribution, and whether the value came from the library or from your override.

One caveat that applies to both: all K values are referenced to the actual duct velocity pressure of this single run. A fitting whose published K is referenced to a different velocity — a branch take-off referenced to the combined upstream flow, for example — needs that conversion done before the value is entered here.