Circuit and load inputs — MEP Tools

Every field in stage 01 "Circuit & load" — circuit type, voltage, voltage-drop criterion, protective device, load, power factor, parallel runs, and length.

Stage 01 Circuit & load is the first of the two input stages. Filling these in does not calculate anything by itself — press Calculate (or Load a worked example) once both stages are set. See Getting started for the full calculate/recalculate flow.

Circuit type

A segmented control: DC / 1-ph AC / 3-ph AC. Changing it also syncs the circuit arrangement used in stage 02 (cable selection).

Nominal voltage

Nominal voltage (V) — the system voltage used to compute design current from a kW/kVA load and to express the voltage-drop percentage. Must be greater than zero, and cannot exceed the BS 7671 low-voltage scope this tool's Appendix 4 tables are drawn from: 1000 V for AC circuits, 1500 V for DC. A value above that ceiling is blocked, not just flagged — there is no applicable table data past it.

Voltage-drop limit

A select (Voltage-drop limit) that sets the allowable voltage-drop percentage:

OptionAllowable VD
BS 7671 Table 4Ab — lighting (3 %)3%
BS 7671 Table 4Ab — other uses (5 %)5%
Custom / project specificationyou type the value

Choosing either BS-referenced option writes the matching percentage into the Custom limit field described below (it stays read-only until you switch to Custom). Selecting Custom / project specification reveals Custom limit as an editable field.

The panel displays this scope note next to the field:

Private-supply whole-installation 6%/8% limits and optional >100 m uplift are not applied.

That is, the two BS-referenced options only implement the BS 7671 Table 4Ab public LV supply / final circuit row (3% lighting, 5% other) — the same row the tool's formula-audit trail cites by name ("Public/final-circuit lighting" / "Public/final-circuit other"). The private-supply whole-installation limits and the optional uplift for runs over 100 m are not available — if your circuit falls under those provisions, select Custom / project specification and enter the applicable percentage yourself.

Custom limit

Only shown when Voltage-drop limit is set to Custom / project specification. The percentage voltage-drop limit used in the pass/fail check. Must be between 0.1% and 30%.

Protective device type

A select with five BS-referenced device types:

The adjacent current field's label changes with the selection:

Device typeField label
MCCB - BS EN 60947-2Long-time trip setting (symbol Ir)
all othersProtective device rating (symbol In)

The field offers a list of standard ratings — 6, 10, 13, 16, 20, 25, 32, 40, 45, 50, 63, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600 A — as suggestions, but you can type any other positive value.

For MCCB, the value you enter is a user-supplied long-time trip setting (Ir) that the tool treats directly as the device's In for the coordination and capacity checks. The tool does not check trip curves, I2, frame/setting range, breaking capacity, discrimination/ selectivity, earth-fault loop impedance (Zs), or disconnection time — verify the entered value against the installed trip unit yourself.

For Semi-enclosed fuse - BS 3036, the tool applies a protective-device factor Cf = 0.725 to the required cable capacity (Cf = 1.00 for all other device types). See Correction factors for how Cf combines with the other correction factors.

Load

A single Load field with an inline unit selector — kW, kVA, or A — next to it. The number you enter is read in whichever unit the selector is set to. Must resolve to a design current greater than zero.

For an AC circuit with kW or kVA selected, the design current is derived using the Power factor field below. For a DC circuit with kW selected, design current is P / Vn and power factor is not part of the formula (see Method and formulas).

Power factor (lagging)

Always shown and required, for every circuit type including DC — the field does not hide when you pick DC. The tool supports lagging power factor only. Valid range: greater than 0 and no more than 1. DC's own design-current and voltage-drop formulas do not use the value, but the field must still hold a valid entry before the result panel commits.

Parallel runs

A positive integer — the number of cable runs in parallel carrying the load between them. Parallel runs assume identical cables, routes, lengths, and terminations, with equal current sharing between runs. Must be a positive integer (≥ 1).

Run length and Length unit

Run length — the single-direction cable run length, must be greater than zero. Length unit — m or ft, selects the unit the length value is entered in.

Validation summary

RuleApplies to
Must be greater than zeroNominal voltage, design current (derived from load/kW+PF/kVA), run length, protective-device rating
Must not exceed the BS 7671 LV scopeNominal voltage — up to 1000 V for AC circuits, up to 1500 V for DC
Must be a positive integerParallel runs
Range 0.1%-30%Custom limit (only enforced when Voltage-drop limit is set to Custom)
Range 0 < pf ≤ 1Power factor (required for every circuit type)

Any failed rule shows an inline validation message on the offending field instead of a result. Not a blocking rule: a protective-device rating below the design current does not stop the commit — it is reported as a failed Device coordination check inside the result instead, alongside the other two checks. See Reading the result.