Frequently asked questions — MEP Tools

Common questions about scope, standards, inputs, and results for the Voltage Drop & Cable Size Checker.

Which standard does this tool use?

BS 7671 Appendix 4, for copper conductors only. Ampacity, correction factors, and (unless you override it) the voltage-drop coefficient all come from Appendix 4 tables. See Method and formulas for the exact equations.

Does it check short-circuit withstand or earth-fault loop impedance (Zs)?

No. Adiabatic (I²t) short-circuit withstand, Zs, and disconnection times are not calculated. See Limits and what is not checked for the full list of what falls outside the tool's scope.

Can I use manufacturer cable data instead of the BS tables?

Yes. The Manufacturer override panel lets you enter AC resistance and reactance (R + X) per conductor, or a direct mV/A/m value, in place of the tabulated voltage-drop coefficient. The current-capacity check still runs against the BS 7671 tabulated ampacity regardless of which coefficient source you choose.

Why did the cable-size comparison table disappear?

A manufacturer coefficient (R + X or direct mV/A/m) applies only to the specific cable it was measured for, so the tool cannot use it to evaluate other sizes in the family. The comparison table is disabled whenever a manufacturer override is active — switch the coefficient source back to BS table values to restore it.

What voltage-drop limit does it apply?

Whichever you select under Voltage-drop criterion: 3% for public/final-circuit lighting, 5% for public/final-circuit other, or a value you type under Custom. The BS-referenced presets come from Table 4Ab, public LV supply / final circuit only — private-supply whole-installation limits (6%/8%) and the optional uplift for runs over 100 m are not applied. Use Custom if your circuit needs one of those. See Method and formulas.

Do I need an account to use it?

No. Calculating is free and requires no sign-in. An account is only needed to save a project or export a PDF report. See Getting started.

Does it size aluminium conductors?

No. The tool covers copper conductors only — there is no aluminium data path anywhere in the calculation.

What does the MCCB "Ir" field mean?

For MCCB - BS EN 60947-2, the field is labelled Long-time trip setting (Ir), and whatever you enter is used directly as the device's In for the coordination and current-capacity checks. The tool does not check the trip curve, I2, breaking capacity, or frame/setting range against an actual trip unit — verify the entered value yourself. See Limits and what is not checked.

Why does a result say "PASS" but the tool still shows warnings?

A pass means the three implemented checks (device coordination, corrected capacity, voltage drop) succeeded for your inputs — it is not a full BS 7671 compliance declaration. The warnings panel lists standing scope notes (such as the voltage-drop limit basis or a manufacturer-override reminder) and any condition-specific flags, and they apply whether the overall result is a pass or a fail.