Load the worked example or enter your own circuit, press Calculate, and read the result.
Open Voltage Drop & Cable Size Checker from the tools catalog. No sign-in is needed to calculate — you only need an account to save projects or export a PDF report.
The page is a single column: three input stages (01 Circuit & load, 02 Cable selection, 03 Installation corrections) with the result panel beneath them. The tool opens blank — nothing is pre-filled, and nothing calculates automatically as you type. You fill in the stages (or load the worked example below), then press Calculate.
With no result yet, the result panel shows a start zone:
Your result appears here
A pass/fail verdict, the smallest size that works, a size-by-size comparison and every formula step — produced from the inputs below when you press Calculate.
- Enter the circuit 2. Calculate 3. Save it — free account
Load a worked example Fills a typical 400 V submain and runs it. Nothing is saved until you say so.
Press Load a worked example to fill both stages with a preset circuit and run it immediately — you don't press Calculate separately; loading the example calculates it.
01 Circuit & load
| Field | Value |
|---|---|
| Circuit type | 3-ph AC |
| Nominal voltage | 400 V |
| Voltage-drop limit | Custom / project specification |
| Custom limit | 5 % |
| Protective device type | MCB - BS EN 60898 |
| Protective device rating | 80 A |
| Load | 45 kW |
| Power factor (lagging) | 0.85 |
| Parallel runs | 1 |
| Run length | 65 m |
02 Cable selection
| Field | Value |
|---|---|
| Cable construction | 4E4 (multicore XLPE armoured) |
| Installation method | Clipped direct, reference method C |
| Circuit arrangement | 3ph |
| Cable size | 35 mm² |
| Ambient temperature | 30 °C |
| Grouping | 1 circuit |
| Thermal insulation | Not in insulation |
| Manufacturer override | Off — the tabulated BS voltage-drop coefficient is used |
Once it loads, the action rail shows Calculated and an EXAMPLE badge appears next to the Result heading — this is a real, already-run calculation, not a placeholder.

For the worked example above, the result panel shows:
Voltage drop 1.30 %, badge PASSES — 5.21 V drop, receiving end 394.79 V.
Three checks, all PASS: Device coordination (76.41 A ≤ 80.00 A), Current capacity (80.00 A ≤ 154.00 A), Voltage drop (1.30 % ≤ 5.00 %).
Four metric tiles: Design current / run 76.41 A, Corrected Iz / run 154.00 A, Coefficient 1.049 mV/A/m, Max length 249.60 m.
A recommendation: "35 mm² also passes — you are 2 sizes oversized. It gives 1.30 % against your 5 % limit."
A Length headroom bar (65 m of 249.60 m max — 26 % used) and a Size ladder of clickable size chips — picking one recalculates the whole result against that size.
Cable size comparison — "17 sizes evaluated · smallest suitable 16 mm²", with per-row statuses (AMPACITY FAIL, SMALLEST OK, SELECTED, PASS, and so on) and a Show all 17 compatible sizes button that reveals every row.

Calculation steps — an "11 steps" audit trail, with a Summary / Full audit trail toggle.
Assumptions and warnings — a collapsible panel of any run-specific notes plus the standing disclaimers.
A Report section offering Print / Save as PDF and Export branded PDF (the latter carries a PRO badge on free accounts).
Change any input once a result is showing, and the action rail switches from Calculated to Recalculate — the figures on screen do not update yet. A strip above the result reads "Inputs changed. You're looking at the previous run." until you press Recalculate.