Limits and what is not checked — MEP Tools

The exact boundary of what the checker verifies, what it does not, and the assumptions behind every result.

The tool implements three specific checks against BS 7671 Appendix 4, for copper conductors. Everything below states that boundary plainly, so a pass is never read as more than it is.

What is checked

  1. Protective-device coordination — Ib ≤ In ≤ Iz.
  2. Corrected current-carrying capacity — the tabulated ampacity of the selected cable, derated by the installation-condition correction factors (Ca, Cs, Cd, Cg, Ci, Cf, Cc, Ccores), against the protective-device rating.
  3. Voltage drop — the calculated drop along the run against the selected voltage-drop limit (3% lighting / 5% other / custom).
  4. Smallest-passing-size search — within the selected cable family, installation method, and circuit arrangement, the tool identifies the smallest size that passes both the current-capacity and voltage-drop checks (disabled when a manufacturer coefficient override is active — see below).

See Method and formulas for the exact equations behind each of these.

What is not checked

Assumptions

Disclaimer

The tool displays this notice, verbatim, alongside every result:

For engineering guidance and checking only. Final cable selection must be verified by a qualified professional using the applicable code edition, local amendments, manufacturer data, and authority requirements.